Customer Pain Points

Renewable power output is hard to predict, with volatile prices and unstable returns.

Difficult renewable absorption, high curtailment rates, and reduced returns.

Insufficient plant flexibility and weak ancillary-service revenue.

Solution
Key Functions

Track scheduled generation and smooth output fluctuations.

Optimized coordination of renewables and storage with energy time-shifting.

AGC/AVC capabilities for fast grid peak and frequency response.

Customer Value

Participate in power market trading to increase project returns.

Enhanced frequency and peak regulation for better grid stability.

Improve renewable absorption, cut carbon emissions, and stay eco-friendly.

Technology Advantages
Safety

Multi-level fuse protection, millisecond-level linked protection, online insulation monitoring.

Intelligent three-level fire alarm, PACK-level detection + water suppression.

Real-time thermal runaway warning, multi-level pressure relief & explosion prevention.

Cost-Effectiveness

Long-life LFP cells and high-precision SOX algorithms for higher ROI.

Overall efficiency up to 88%, DC-side efficiency ≥93%.

Intelligent liquid cooling keeps cell temperature ≤35°C with ≤3°C difference, cutting auxiliary power by 10%.

Reliability

AI-based predictive maintenance reduces unexpected downtime by 90%.

Remote diagnosis & upgrades; over 90% of issues resolved online.

Modular design shortens replacement time and improves maintenance efficiency.

Technical Data
CategorySpecification
Cell CapacityLFP 314Ah
System Configuration12P*416S
Voltage Range1164.8 ~ 1497.6Vdc
Charge/Discharge Rate0.5P
Rated Energy5.015MWh
Rated Power2.508MW
Dimensions (W×D×H)6058x2438x2896mm
Weight<42.5t
Charge/Discharge Efficiency≥93%
Protection RatingIP55 (battery compartment)
Thermal ManagementIntelligent Liquid Cooling
Fire Suppression SystemAerosol + Water
Communication ProtocolCAN/RS485/Ethernet
Operating Temperature Range-30°C~+50°C(derated below -45°C)
Storage Humidity0-95%(non-condensing)
Noise≤75dBA
Max Operating Altitude4000m(> 2000m derated)