Difficult renewable absorption, lack of storage facilities, and insufficient flexible regulation resources.
Difficult renewable absorption, lack of storage facilities, and insufficient flexible regulation resources.
High supply-demand balancing pressure with insufficient peak and frequency regulation.
Weak transmission and distribution capacity and high grid investment costs.
Primary frequency regulation plus AGC/AVC for fast grid command response.
Low-charge/high-discharge arbitrage in the energy market while smoothing price swings and optimizing supply-demand balance.
Supports black-start capability.
Participate in medium/long-term trading, spot trading and ancillary services to boost returns.
Improve renewable absorption and add flexible regulation resources.
Enhance transmission and distribution, ease supply-demand pressure, improve peak regulation, and defer grid investment.
Multi-level fuse protection, millisecond-level linked protection, online insulation monitoring.
Intelligent three-level fire alarm, PACK-level detection + water suppression.
Real-time thermal runaway warning, multi-level pressure relief & explosion prevention.
Long-life LFP cells and high-precision SOX algorithms for higher ROI.
Overall efficiency up to 88%, DC-side efficiency ≥93%.
Intelligent liquid cooling keeps cell temperature ≤35°C with ≤3°C difference, cutting auxiliary power by 10%.
AI-based predictive maintenance reduces unexpected downtime by 90%.
Remote diagnosis & upgrades; over 90% of issues resolved online.
Modular design shortens replacement time and improves maintenance efficiency.
| Category | Specification |
| Cell Capacity | LFP 314Ah |
| System Configuration | 12P*416S |
| Voltage Range | 1164.8~1497.6Vdc |
| Charge/Discharge Rate | 0.5P |
| Rated Energy | 5.015MWh |
| Rated Power | 2.508MW |
| Dimensions (W×D×H) | 6058x2438x2896mm |
| Weight | <42.5t |
| Charge/Discharge Efficiency | ≥93% |
| Protection Rating | IP55 (battery compartment) |
| Thermal Management | Intelligent Liquid Cooling |
| Fire Suppression System | Aerosol + Water |
| Communication Protocol | CAN/RS485/Ethernet |
| Operating Temperature Range | -30°C~+50°C(derated below -45°C) |
| Storage Humidity | 0-95%(non-condensing) |
| Noise | ≤75dBA |
| Max Operating Altitude | 4000m(> 2000m derated) |